Water quality monitoring checklist
Form code: F-07 Project: …… | Water official: ……
7–1. Birth certificate of water management program
title | Information |
|---|---|
User type | Non-contact / interactive and contactable decoration |
Compensatory water source | …… |
The volume of water is the basis of calculations | …… cubic meter |
Actual flow rate of treatment | …… cubic meters per hour |
Turnover Time | …… |
Filter type | …… |
The main disinfection method | …… |
Additional disinfection method, if any | …… |
Responsible for determining control limits | …… |
Reference control limits | …… |
Sampling points | …… |
Laboratory of the contracting party | …… |
Pollution response program number | …… |
7–2. his foot form
parameter | unit | The approved limit of the project | the result | Sample time and place | action |
|---|---|---|---|---|---|
water temperature | °C | …… | …… | …… | …… |
pH | — | …… | …… | …… | …… |
Residual disinfectant according to method | mg/L | …… | …… | …… | …… |
Total chlorine, if applicable | mg/L | …… | …… | …… | …… |
Turbidity | NTU | …… | …… | …… | …… |
Electrical conductivity or TDS | Device unit | …… | …… | …… | …… |
ORP, if used | mV | …… | …… | …… | …… |
Filtration flow rate | m³/h | …… | …… | …… | …… |
Filter pressure difference | bar | …… | …… | …… | …… |
UV status, if any | According to the device | …… | …… | …… | …… |
Prescribed microbiological test | According to the method | …… | …… | …… | …… |
ORP is not a substitute for direct measurement of residual disinfectant. ORP limits should be interpreted with system type, pH and monitoring method.
7–3. Visual and functional inspection
item | the result | action |
|---|---|---|
The water has no turbidity or unusual discoloration | …… | …… |
Checked for unusual smell | …… | …… |
Algae or biofilm on surfaces examined | …… | …… |
Particles, leaves and debris are collected | …… | …… |
Circulation and filtration are active | …… | …… |
Injection equipment, sensors and materials are ready | …… | …… |
There is no chemical leakage | …… | …… |
Stagnant water is not collected in unwanted places | …… | …… |
The material containers are labeled and the incompatibility of the storage has been checked | …… | …… |
Sampling equipment is valid and clean | …… | …… |
The previous corrective action is closed | …… | …… |
7–4. The difference between a decorative and interactive fountain program
For decorative fountains, CDC emphasizes sediment and biofilm management, temperature, water retention, and residual disinfection. Monitoring of important parameters is recommended at least weekly, and the condition of the environment or design may require more frequency. Observation of apparent contamination should enable corrective action. CDC Guidelines for Decorative Fountains [446]
For water playgrounds, CDC operational guidelines state the following:
subject | The amount or frequency listed in the guide |
|---|---|
pH | 7.0 to 7.8 |
Free chlorine without using cyanuric acid | At least 1 mg/L |
Free chlorine if cyanuric acid is used | At least 2 mg/L |
Go to the whole system | At least 3 mg/L |
Disinfectant and pH control | Before reopening and every 2 to 4 hours during operation |
circulation time | 30 minutes or less |
Equipment performance inspection | Daily before reopening |
These values are not the upper limit of the material or the license to use the stabilizer; The approved plan, material limit, manufacturer's order and local authority regulations must be followed simultaneously. Guidelines for the operation of CDC water playgrounds [447]
7–5. Registration of non-compliance
Time to discover | problem | Restriction or suspension imposed | corrective action | Retest result | Permission to reopen |
|---|---|---|---|---|---|
…… | …… | …… | …… | …… | …… |
In the event of pollution, the amount and method of correction should be extracted from the approved instructions of the same system. Experimental addition of chemical without measuring and recording is not a water quality control method.
Notes and references
Source 12: CDC Guidelines for Decorative Fountains; www.cdc.gov. Full address in the bibliography.